UPS COVER BASIC 1K
COVER Online Double-Conversion uninterruptible power supply, 1kVA/0.9kW. Plug@Play. Tower cabinet (without batteries). 1:1 phase configuration.
Diesel generator set ESE 17 TBI
CHARACTERISTICS
- The ESE 17 TBI diesel generator produced by Endress Group Romania under the Zenessis brand is equipped with BAUDOUIN 4M06G20/5 engine, Stamford SOL1-P / Strathon ECO-17KW alternator and INTELI LITE AMF 25 control system, which ensures the starting of the generator, the control of the parameters, in manual or automatic system. The generator can be supplied with remote control and monitoring as well as other options. Zenessis power generators are guaranteed for 60 months, up to 3000 operating hours.
|
|
ENGINE
Specifications | Value | Baudouin diesel engine |
Model | 4M06G20/5 |
|
Number of cylinders | 6 in linie | |
Induction system | Natural aspiration | |
Cooling system | With water | |
Maximum standby power (kWm) | 20 | |
Speed (rpm) | 1500 rpm | |
Cylinder | 2.3 (I) | |
Bore & Stroke (mm) | 89 x 92 mm | |
Compression factor | 17.5 : 1 | |
Regulator | Mechanic | |
Total oil capacity (l) | 9.5 (I) | |
Cooling agent capacity | 5 (l) | |
Fuel consumption at 100% load (l / h) | 4,1 (l / h) |
STANDARD FEATURES
Specifications | Value | Alternator |
Model | Stamford SOL1-P / Strathon ECO-17KW |
|
Frequency (Hz) | 50 Hz | |
Concept | Brushless, 4 poles | |
Phases | 3 | |
Voltage (V) | 400 / 230 V | |
Protection class | H | |
Excitation system | Electronic | |
Performance | 93% | |
Protection | IP23 | |
Certification test | test EN 10204:2001 |
CONTROL PANEL
|
|
CONTROL PANEL STANDARD SPECIFICATIONS
|
|
|
COMMAND MODULE STANDARD SPECIFICATIONS
|
|
COMMAND MODULE CONFIGURATION
|
|
Engine – engine speed; oil pressure; coolant temperature; running time; battery voltage; maintenance data. |
Alternator – voltage (L – L, L – N); current (L1 – L2 – L3); frequency; kW; Pf; kVAr; kWh,kVAh, kVarh; phase sequence. |
Main network – voltage (L – L, L – N); frequency, mains ready; mains off; generator set ready, generator set disconnected, active power kW, apparent power kVA, reactive power kVA r, power factor, phase sequence. |
Warning – battery faulty charging, low battery voltage, fail to stop, low fuel level, overload, phase reversing, speed sensor failure. |
Alarms – low oil pressure, high engine temperature, under / over voltage, under / overfrequency, under / overvoltage, ECU fault -optional. |
Status displays – missed start, emergency stop, low oil pressure, high engine temperature, under / overspeed, under / overfrequency, under / overvoltage, oil sensor, phase rotation, overload, overcurrent group, phase reversal. |
STATIC BATTERY CHARGER:
Made with TSD technology, with high efficiency. Protected for short- circuit currents, it can be used as a current source, input voltage 196-264 V, output voltage 27.6 V / 5A or 13.8 V / 5A.
STANDARDS
Electrical safety / EMC, BS EN 60950; BS EN 60950 – 6 – 2 EMC; BS EN 61000 – 6 – 4 EMC.
HOUSING
|
|
|
|
DEMENSIONS AND WEIGHT OF OPEN GENSET
|
|
DEMENSIONS AND WEIGHT OF THE CLOSED GENSET
|
|