• Pack

UPS COVER BASIC 1K (2x9Ah)

COVER Online Double-Conversion uninterruptible power supply, 1kVA/0.9kW. Plug@Play. Tower cabinet (without batteries). 1:1 phase configuration.

UPS equipped with 2 x 9Ah batteries.

11-Z-BASI-102009

CHARACTERISTICS

  • True OnLine technology Double Conversion (VFI according to IEC62040) provides excellent voltage performance with a sinusoidal shape, regardless of power disturbances and the type of consumers being powered.
  • Statis switch bypass (Static Switch type) ensures uninterrupted power supply to loads in critical situations such as overheating or failure.
  • Communications:
  • - USB and RS232 for monitoring and managing the operation of the power supply and receivers,
  • - An expansion card slot allows connection of an SNMP card to manage and monitor the UPS on the network.
  • LCD control panel clearly informs about the operating mode, power supply parameters and allows you to configure UPS parameters.
  • Small dimensions, As a result, minimal space is required to install the device.
  • High efficiency of the device minimizes energy consumption and reduces the emitted heat, which makes the eventual cooling of the premises cheaper.
  • ECO mode (enhanced efficiency mode) allows for 99% efficiency and additional energy savings.
  • CVCF frequency converter mode allows the power supply to operate in output frequency conversion mode to 50 or 60Hz for powering non-standard loads.
  • Automatic diagnostics guarantees the full efficiency of the device, control of components and operating parameters without user intervention.
  • Wide range of input voltages for normal operation means that the use of batteries by the UPS is limited to the minimum necessary, practically only in cases of complete power failure.
  • TOWER compact housing makes the UPS space-saving and suitable for installation both under desks and in space-constrained areas.
  • High output power factory guarantees even more active power compared to other power supplies in this class.
  • Wide input frequency range in normal operation makes it possible to freely use the power supply in a mixed network of the city grid - generator type.
  • Autorestart guarantees maintenance-free operation of the device in case of long power outages.
  • Battery start (so-called cold start) gives you the ability to start the power supply even in the event of a complete lack of supply voltage.
  • Advanced battery management guarantees optimal charging and utilization of battery banks, extends battery life by 50% and reduces operating costs.
  • Excellent voltage quality , achieved through the use of high-frequency PWM modulation, makes it possible to deliver a voltage with extremely stable parameters, regardless of power disturbances and the type of powered devices.
  • Overload resistance is the certainty of power supply in the presence of transients and high tolerance to operating errors.
  • Advanced software enabling the user to have full control over the device and the powered loads
  • EPO connector provides the ability to remotely shut down the power supply in the event of a fire, for example - optional equipment.

BACKUP TIME

Internal batteries Load Backup time [min]
BASIC 1K
2 x 9Ah 100% 4
75% 7
50% 12
25% 30

TECHNICAL SPECIFICATIONS

Model BASIC 1K
Power 1kVA / 0,9kW
Phases In/Out 1:1
Input
Nominal voltage 208 / 220 / 230 / 240 Vac
Voltage range 110 ÷ 300 Vac
Nominal frequency 50 / 60Hz
Frequency range 47 ÷ 63 Hz
THDi <3%
Input power factor ≥0,99
Output
Nominal voltage 208 / 220 / 230 / 240 Vac
Power factor 0.9
Voltge regulation static/dynamic ±1% / ±3%
Nominal frequency 50 / 60 ± 0,05 Hz
Overloads capability 110% - 10 min., 130% - 60 s., >130% - 3s.
Efficiency in OnLine mode >90%
Efficiency in ECO mode 99%
Crest factor 3:1
Switching time 0ms
Output sockets 3 x IEC320 C13
Batteries
Cold start Yes
Internal batteries possibility 2 x 9Ah/12V
Nominal voltage 24Vdc
Charger curent 1,5A
Charging time 3 – 8 hours up to 90% capacity (configurable)
Charging cycle According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control.
Dimensions and weights
Dimensions (S x G x W) 145 x 282 x 220 mm
Weight 9,8 kg
Signaling and communication ports
Operating status indicator LCD + audible alarm
Communication RS232, USB, slot SNMP
Environmental conditions
Noise level <49 dB
Operating temperature for UPS 0°C ÷ 45°C
Recommended operating temperature 15 °C ÷ 25 °C
Storage temperature -25°C ÷ 55°C
Humidity 0 ÷ 95% (non-condensing)
Cerifications
Interference immunity EN 62040-2:2005, EN 62040-2:2006
Safety IEC62040-1-1, CE, 62040-3 :2001
Optional accesories
- SNMP card
- RS485 card (Modbus)
- AS 400 mini (dry-contact) card
- Environmental sensor (EMD)
- Remote Emergency Power Off button
- Remote LCD panel

Due to constant product improvement all specifications are subject to change without notice.

Related Products

Related Products ( 9 other products in the same category )